EN1154 and EN1155 Standards

A Guide to EN 1154 and EN 1155.

Back

EN 1154 and EN 1155 are European standards that regulate the performance, safety, and testing of door closing devices.

EN 1154

EN 1154 is the harmonised European standard for controlled door closing devices. It sets out product types and a clear six-digit classification system to describe a closer’s intended use and performance.

What EN 1154 covers:

  • Intended use and product type
  • Number of test cycles (durability)
  • Suitable door mass
  • Corrosion resistance
  • Performance requirements (closing force, speed, etc.)
  • Six-digit classification code summarising the above
test

EN 1155

Electromagnetic hold open door closers for hold open or swing free doors must meet the additional requirements of EN 1155. Commonly used on fire doors, these devices are specified where a hold open or swing free function is needed for example in high traffic areas for convenience or where it is difficult to meet the maximum opening force requirements of Part M of the Building Regulations.

When linked to the building’s fire alarm system, the electromagnet disengages when the alarm sounds or if power is lost, allowing the door closer to close the door automatically and restore its fire resisting function.

EN 1554 / EN 1155 Standard and CE Classification.

Below is a breakdown of how each of the criteria is measured as part of the classification.

Fire Doors

Within EN 1154, certain recommendations are made for choosing devices used on fire door assembles. These include:

  • Closers size 1 and 2 are NOT suitable for use on fire doors.
  • Door closers shall not include a mechanical hold open device or clip on a fire door unless it is an electrically powered device connected to the building fire alarm system.
  • Control regulators shall be either concealed or operable only by means of a tool.

Closing Force vs Opening Force

The closing force required to fulfill the life saving fire-safety function demanded by EN 1154 can, for some elderly or disable people, be difficult to overcome and the door can become a barrier to safe and easy access for them.

Within the detail of BS 8300 and Approved Doc M of Building Regulations, there is a requirement to achieve low opening forces to satisfy the need for easy and universal accessibility. As a consequence there is a conflict between the required closing force for fire safety and the desirable opening resistance which requires special consideration in the specification process.